    Data Center Map

    AdNet - DataCity Bucharest


    » Index » Romania » Bucharest » AdNet - DataCity Bucharest

    AdNet - DataCity Bucharest is located in the area Bucharest, Romania, and the colocation data center is carrier neutral. The data center was last updated on 04-07-2017.


    Address:
    AdNet Telecom
    Blv. Pipera, Nr.1/VI
    077190 Voluntari
    Ilfov, Romania

    » Request quote
    » Visit website

    Click here to find other data centers
    owned and operated by AdNet Telecom.


    Profile
    Gallery
    Tenants
    Connectivity
    Request quote
    Office space
    Rack Cabinets
    Dedicated Servers
    Suites
    Footprints
    Virtual Servers
    Cages
    Hosting of individual servers
    Remote Hands

    Profile


    TIER III DESIGN:
    Availability higher than 99.982%
    Redundant power elements with independent
    circuits paths configured in as 1+1
    Redundant cooling elements with
    independent circuits paths configured in as N+1
    Provides concurrent maintenance

    ENERGY EFFICIENT:
    Optimized IT Equipment arrangement in Cold/Hot Aisle
    Advanced multistep cooling control allow for high efficiency
    Integration of green energy such as photovoltaic and wind turbine
    High performance rectifiers, inverters and accumulators in UPS system
    Targeted PUE - Power usage effectiveness lower than 1.3 for 100% load
    Actual PUE - 1.75 at 20% Load

    IT & TELECOM INFRASTRUCTURE:
    IT infrastructure design for TIER III
    Multipath optical fiber on 3 circuits
    High end border routing equipment Juniper MX series
    Data Center L2 and L3 switching performed by Cisco Nexus
    Complex evolved virtualization platform based on Cisco UCS, HP 3PAR
    storage and VMWare VCenter/Vsphere
    Cluster balancing technology from A10 Networks
    Advanced traffic anomaly detection and cleaning with Arbor System technology
    Complete internal data circuits distribution with Panduit materials

    COOLING:
    Adiabatic & Free cooling - Indoor for IT Containers:
    60 racks with average power of 7 KW arranged in 3 cold aisle with 20 racks each resulting in a total power of 140KW / cold aisle
    24 LCU providing 20KW of cooling arranged in 3 cold aisle resulting in 8 units / row with a capacity of cooling of 160KW (7+1)
    In-line positioning with racks, Cold-Isle/Hot Isle containment with front to back airflow
    Cooling agent: thermic agent with heat transfer properties optimized for whole range of meteorological conditions
    Chiller water cooling - Outdoor:
    3 x 300KW chiller units with Free Cooling mechanism
    "Air-Conditioning" type water cooling - compressors based in 12 steps (4 independent compressors / chiller unit)
    N+1 Redundant compressors, ventilators and other components (according to TIER III standards for cooling)
    Automation system for adjusting electrical energy consumption
    Adiabatic & Free cooling - Indoor for Power containers
    4 units 30KW
    N+1 redundancy type according to TIER III standards for power supply

    POWER & UPS:
    Total installed power 480 kW x 2 with redundancy in 2 lines
    2 automatic back-up diesel generators one for each line
    Accumulators pack - 108 with 100 Ah capacity for each power box
    2 UPS of 40 kVA for chiller pumps
    2 UPS of 20 kVA for interior modules of inline cooling units
    2 heating pumps and 1 ice pillar for extra heat removal before Chillers
    1 wind turbine with 2 KW - providing auxiliary power
    80 x 250W (20 KW) photovoltaic farm - compensating in extra hot summer days

    RACKING & VIRTUALIZATION:
    Racks
    Hardened steel Racks:
    45U racks space proving at least 42U usable IT Equipment
    Depth: 1000mm
    Width: standard 19''
    PDU: for each Rack 2 PDU three-phase power supply of 400V - Maximum power 11 KW redundant/ Rack, each PDU with 24 IEC13 sockets and 6 IEC19 sockets
    Assembling on metallic anti vibration and anti seismic system

    Virtualization system
    Cisco UCS Blade Server System
    5 x Blade server chassis each with 8 blade server units installed
    Installed processing power ~ 1800 VCPU
    Installed memory : 7168 GB
    HP 3PAR 7400 Enterprise Storage Dual controller with 200TB of usable space (250TB installed)
    Storage: even mix of SAS/NL-SAS disk
    Switching: Integrated Cisco switch fabric with extra 32 port 10GB for external connectivity
    VMWare VSphere/VCenter Enterprise plus virtualization system

    SECURITY SYSTEM:
    Complex security system
    Fire detection system
    Smoke detection sensor
    Temperature sensor
    Fire extinguisher cylinders
    Fire detection station
    Exterior fire alarm control panel from fast access from outside
    Dual power source, both from main power supply and UPS
    Access control module
    Emergency fire path - both mechanical and electromagnetic
    Magnetic stripe card access
    Unlimited user access with multiple roles and rights
    Control panel integration with fire detection and extinguisher system - automatic fire path unlocking
    Real time reports and history : access type, users, access path, etc.
    Surveillance system
    HD IP cameras
    NVR recording and monitoring
    Minimum 30 days data storage in

    INFRASTRUCTURE MANAGEMENT:
    Complex monitoring and management software suite integrating all hardware and software components installed in the datacenter infrastructure (power elements, cooling elements, security & surveillance, sensors & monitoring devices)
    Data center components detailed charts and schematics (racks, cooling, power, surveillance, control access, sensors, etc.)
    IT Equipment layout
    Power supply, circuits and distribution
    Chillers, LCU, cooling paths
    Surveillance, access control, firefighting systems
    Humidity, temperature, air quality, flood sensor system
    Renewable energy controllers
    Real time & Historical monitoring for all managed systems
    Statistics, Graphics and Analysis of various parameters
    Friendly graphical web user interface compatible with most modern browsers

    CONNECTIVITY:
    Physical connections (L1):
    3 paths geographically and logically independent underground optical fiber links - 144 optical wires available
    Open Third-party fiber optic interconnection cabinet easily accessible from any underground infrastructure
    Logical connections (L2-L3):
    Data center node is included in main N x 10Gbps metropolitan multi-ring core network of 2K Telecom, providing high capacity resilient communications with most POP or exchange nodes
    Juniper MPLS Switches and Routers provide any type of logical connection (L2 circuits, VPLS, L3 VPN, QinQ, Dark Fiber, TDM transport, etc.)
    External connections (National&Internet)
    2KTelecom is member of public Internet Exchanges: Interlan, Balkan-IX RoNIX, NxData, IBM Data Center, INES Datacenter, Cyberhost Datacenter
    Extra private national interconnection with leading ISP providers improve capacity and latency
    Optimized Balanced Access to Internet is achieved through major world wide Internet Carriers (M247/NTT, Telekom/LEVEL3)








    AdNet - DataCity Bucharest Pricing/Quotes


    If you are interested in receiving a quote for AdNet Telecom, please try our free quote service.